System Sensor OSI-R-SS,Reflective Beam Smoke Detector
OSI-R-SS is a 4-wire, single-ended, reflective beam smoke detector including an 8" reflector and an integrated sensitivity test , housing construction : ABS plastic ,Color painted white , offer price list : beam smoke detector : 890,000 VND , addressless beam smoke detector all kinds of prices : 5% off - 780,000 VND ,beam smoke detector det-640rb : 1,089. 000 VND , projector beam smoke detector i-9105r, c-1006r : 1,890,000 VND
Featured
• Combo transmitter/receiver
• 12° . wide field of view
• Quick, easy and intuitive beam alignment indicated by diagonal arrow LED direction
• Long range coverage of 5-100 m (16-328 ft) is standard; No separate range kit required
• High resistance to movement of the building; withstand movement +/- 1°
• Withstand strong light sources; No alarm when saturated by sunlight
• Protection against ingress of solid objects • Automatic sensitivity threshold level setting
• Horizontal 50° and vertical 20° . beam adjustment
• Built-in image heater is standard
• Remote test station capable of testing electronically simulated smoke the ground
• Standby, fault and warning LED indicators are visible the front and bottom
• Automatic drift compensation
• Paintable cover/case
• Removable plug-in terminal block
• Optional heater available for reflector
Specifications sheet
| Physical/Operating Specifications | |
| Dimensions of the detector | Height 6 ”(152,4 mm); Width 10 ”(254 mm); Deep 4,5 ”(114,3 mm) |
| Dimensions (reflector) | Height 9,06 ”(230 mm); Withd 7,87 ”(200 mm) |
| Detector weight | 2.48 lbs (1.12 kg) |
| Total weight | 3.91 lbs (1.77 kg) |
| Measuring wires for terminals | 14 AWG (2.08 mm²) |
| Electrical Specifications: OSI-R-SS, OSI-RA-SS | |
| Operating voltage | 10.2 to 32 VDC (nominal 12 or 24VDC) |
| Maximum standby current | 7 mA @ 32 VDC, 11 mA @ 24 VDC, 20 mA @ 12 VDC, 50 mA @ 10.2 VDC |
| Maximum alarm current (LED on) | 11 mA @ 32 VDC, 15 mA @ 24 VDC, 24 mA @ 12 VDC, 54 mA @ 10.2 VDC |
| Environmental Specifications | |
| Operating humidity | 0 to 95% Relative Humidity, Non-condensing |
| Operating temperature | UL listed for use 32°F to 100°F (0°C to 37.8°C) Application temperature range: -20°C to +55°C (-4°F to 131°) F) |
| Operational characteristics | |
| Protection range | 16 ft to 328 ft (5 m to 100 m) |
| Adjustable angle | 20 degrees vertical, 50 degrees horizontal |
| Incident error status | Long term drift reference out of 20% range, beam occlusion or detector misalignment, image saturating. |
| Main house | Arrow LED Direction |
| Lights | Local red LED and remote output |
| Standard | |