QA16, Check the Horing address
The QA series can be in single or 32 ring network configurationsThis system is designed for all applications with the advantages of easy installation, fast and accurate detection and simple maintenance ,The user-friendly HL Fire Tool software saves your time programming , The reliable QA series certainly meets your needs for safety.
Descriptions QA16, Check the Horing address
- Each loop can connect up to 250 addressable devices. The maximum network is 32 rounds and the total number of addressable points is 8000. Large LCD display (40 x 15 lines) allows more events to be displayed on the same screen.
- The repeater can be set to be temporarily isolated.
- Private loop module test feature to save time on panel testing.
- On-board Self-Test feature to simulate alarm output.
- Easy system programming via PC to control panel.
- Event log can store up to 2030 events. Features Optional thermal printer can print out complete board status.
- CE certification
Technical data sheet QA16, Check the Horing address
Model | QA16 |
Power supply | 220 V AC 50 / 60Hz |
Battery capacity | 24 V DC 4AH |
Battery charging voltage | 26V DC 100 ~ 400mA With automatic adjustment function |
Usage voltage | 26,5V DC 340mA |
System capacity | 250 devices / 1 loop |
Trở kháng | less than 40Ω |
Transmission method | Digital transmission |
Latency | 0 ~ 40 seconds Other options available |
Sound | 85dB @ 1M |
Structure | 1.6mm . steel plate |
Color | Gray |
Size (mm) H x W x D | Loop 1 ~ 4: 400 x 500 x 130 Loop 5 ~ 8: 600 x 500 x 150 |