Nohmi FRRU004-MCM MINIATURE monitoring module
Miniature Contact Module (FRRU004-MCM) is used to monitor the contact status of initiating device containing normally open contacts ,FRRU004-MCM can be programmed in the control panel to monitor ,Normal Open or Normally Closed contact on the Fire Alarm Control Panel (FACP),
When the Normally Open contact is selected and the contact is closed, the FRRU004-MCM will report its condition to the FACP. Similarly when the Normally Closed contact is set to the monitor condition and the contact is opened, the FRRU004-MCM will report its condition to the FACP. The FRRU004-MCM monitors an open circuit of wiring connected to terminal C and contact NO (NC). The FRRU004-MCM is commonly used to monitor traction stations and other equipment where the module is installed in an electrical box or enclosure. The contact uses a shielded terminal block in accordance with UL requirements to protect against accidental failure and ground fault.
Feature Nohmi FRRU004-MCM MINIATURE monitoring module
• NFPA Class A (Style 6 & 7) and Class B (Type 4) for SLC
• NFPA Class B (Type B) for IDC
• Set up electronic address
• Small apartment
• Easy to install
Model no. FRRU004-MCM
Specifications Nohmi FRRU004-MCM MINIATURE monitoring module
| No | Descriptions | Specifications |
| 1 | SLC input power supply rated range (S+,S-) | 22.0 to 24.0V |
| 2 | Maximum 24VDC SLC Standby Current (S+,S-) | 250µA |
| 3 | SLC alarm current 24 VDC max (S+,S-) | 250µA |
| 4 | IDC input wiring | Class B (style B) |
| 5 | End-of-line resistor for IDC | 5.1kΩ, 1/2W |
| 6 | Maximum wire resistance IDC | 100Ω |
| 7 | Maximum wire capacitance IDC | 1µF |
| 8 | Temperature | 0°C to 49°C (32°F to 120°F) |
| 9 | Humidity | 0 to 93% (no condensation) |
| 10 | Dimensions | 65.5mm (2.58 inches) (heigth) × 59mm (2.32 inches) (Width) × 24mm (0.94 inch) (Length) |
| 11 | Electrical box applicable for installation | 64mm (2-1/2 inch) deep one cast iron box North America |