Descriptions Guide to choosing the right fire sprinkler
On the surface, sprinkler are designed to be very simple, but a lot of research and production classify them according to NFPA 13 standards for sprinkler system installation in many ways, including temperature ratings, coefficients K, injection direction, reaction type, design and performance characteristics, special service conditions. Some sprinklers are designed to protect storage facilities, and some sprinklers are designed as special application sprinklers.
Hướng dẫn chọn đầu phun sprinkler chữa cháy phù hợp
Instructions for choosing a suitable fire sprinkler head include 02 separate parts as follows:
1. In Part 1 we will introduce to you the basic concepts of Sprinkler spray systems, temperature and K factor, so soon I will explore this article with you. - Basic concepts of Sprinkler Nozzles
- Sprinkler are one of many components that make up a fire sprinkler system. The piping system, including the water pipes to the building, the water pipes, the main pipes, the cross main pipes, and the sprinkler branch lines, together with the associated valves, fittings, and joints, make up the system. Water distribution supplies water to sprinkler heads. Is the final ingredient needed to effectively release “water” to control or extinguish a fire.
- A sprinkler “head” consists of a cast or forged metal frame with an integral orifice or drainage hole at one end and a water deflector at the other end. A temperature-sensitive mercury bulb, or heat element, is mounted in the frame to keep the hole covered and prevent water from draining out of the sprinkler. In the event of a fire, when the mercury ball reaches the limit temperature, it will explode and activate the firefighting water pump system to help prevent fires promptly.
- Choose the appropriate temperature
- To select the appropriate temperature rating for a sprinkler, one must be careful to match the sprinkler's temperature rating to the maximum expected ceiling temperature to avoid inadvertent discharge, Temperature rating, distribution Color-coded categories.
- Additionally, FM Global Data Sheet (FMDS) 3-26, Fire Water System Installation Needs for Nonstorage Sprinkler Properties, requires the use of high-temperature water sprinklers for all dry pipe systems in Section 2.1.1.1.
- K-Factor
- K coefficient is a mathematical constant set by the sprinkler head manufacturer related to the water flow discharged from the sprinkler at a certain pressure. When water is discharged through the sprinkler head, the diameter of the hole and the hydraulic characteristics of the hole determine the flow achieved through the sprinkler at a given pressure. An increase in sprinkler K-factor corresponds to higher flow rate (gpm) at a given pressure, and a decrease in K-factor corresponds to lower flow rate at a given pressure.
- K coefficient can be selected based on water supply characteristics. For supplies with higher available water at lower pressures, higher K-factor nozzles may be used. For water supplies with lower volumes of water available at higher pressures, a smaller K-factor nozzle may be used.
- Additionally, global data sheets NFPA 13 and FM 2-0, 3-26, and 8-9 specify the appropriate K-factor, minimum operating pressure, and number of sprinkler heads (or design area ) is calculated for each applicable design criterion. NFPA 13 further stipulates that (minimum) K = 8.0 sprinklers must be used to protect storage with a density of 0.20 or greater, and (minimum) K = 11.2 sprinklers must be used to protect warehouses with a density of 0.34 or greater.
- In Part 1 of the Guide to choosing the right fire sprinkler head, we shared the basic concept of fire sprinkler heads, choosing temperature and K factor. In Part 2, we will share nozzle direction, reaction type, design and performance characteristics as well as special types of nozzles.
- Spray nozzle orientation
- In general, sprinklers are manufactured to be installed in five basic directions: upward, downward, inclined, oblique wall, and ceiling. - Upward sprinklers are installed with a deflector above the frame so that water flows upward from the opening, hitting the deflector to create an umbrella spray pattern.
- Wall sprinklers are installed with a deflector below the frame so that water flows down from the water pipe opening, hitting the deflector to create an umbrella-shaped spray pattern.
- Horizontal Sidewall sprinklers are installed on the wall near the ceiling. The deflector is oriented parallel to the roof/ceiling and provides a quarter-sphere outward water spray pattern.
- Recessed Sprinklers are installed with all or part of the body mounted in a recessed box.
- Concealed sprinklers are installed with the entire body mounted in a recessed housing with cover to conceal the sprinkler.
5 kiểu hướng đầu phun