GAS FIRE SUPPRESSION SYSTEM NOVEC 1230 YOOKSONG
It is a gas fire extinguishing system made using “NOVEC 1230”, the best eco-friendly clean fire extinguishing agent that can be used continuously in the future, and a nitrogen pressurization system (N.D.S – Nitrogen Drive System) is applied for remote design application. Three types of containers (60L, 90L, 140L) are used for securing space and flexible design of the chemical storage room, and only the extinguishing agent necessary for the protection area is applied with a variable filling method to secure human safety and economy. In addition, it is the best existing gas-based fire extinguishing system that is more reliable and reliable through joint development with “JENSEN HUGHES”, the best design program developer in the United States.
Main locations┃Electricity room, battery room, transformer room, generator room, data room, exhibition room, disaster prevention center, paper warehouse, storage room, data room, radiation room, common area, boiler room, etc.
SPECIFICATIONS
emission method | Global release (central storage, modular) | |
Minimum design concentration | Class A(C) | 4.5 % (0.655 kg/㎡) |
Class B | 6.11 % (0.905 kg/㎡) | |
Maximum permissible concentration | 10 % | |
storage container filling | 60 L | 48 kg to 67.2 kg (variable filling) |
90L | 43.2 kg to 100.8 kg (variable filling) | |
140L | 67.2 kg to 156.8 kg (variable filling) | |
plumbing fee | 360 % | |
spray head | protection height | max 5.0 m, min 0.3 m |
protection area | 144.0 ㎥ | |
Spray head minimum design pressure | 0.36 MPa (3.6 bar) | |
release time | 6 ~ 10 Sec |
division | HFC series | INERT series |
FK-5-1-12 (Novec 1230) |
note | |||
Drug name | HFC-23 | HFC-125 | HFC-227ea (FM-200) |
IG-100 | IG-541 | ||
Domestic Certification | Acquisition of performance certification | Acquisition of performance certification | Acquisition of performance certification | Acquisition of performance certification | Acquisition of performance certification | Acquisition of performance certification | |
Origin of fire extinguishing agent | China, Korea, USA | China, Japan | China, USA | domestic | domestic | USA | |
Overseas certification for fire extinguishing agents | UL FM | UL | UL FM | doesn't exist | doesn't exist | UL, FM marine certification, etc. | |
Digestion Principle | Cooling + subcatalyst | Cooling + subcatalyst | Cooling + subcatalyst | choke | choke | Cooling + subcatalyst | |
economic ratio (Main material + construction material + labor cost) |
77% | 91% | 100% | 97% | 105% | 118% | KF-5-1-12 (Novec 1230) Expensive premium fire extinguishing agent |
human safety (NOAEL standard design safety factor) | 115% | -14% | 27% | 14% | 11% | 122% | Human safety of KF-5-1-12 (Novec 1230) is the best |
environmental | to be regulated | to be regulated | to be regulated | no regulation | no regulation | no regulation | HFC-based gases are expected to be regulated according to the greenhouse gas reduction policy |
When releasing a fire extinguishing agent Impact of internal equipment and buildings | usually | usually | usually | bad | bad | Great | KF-5-1-12 (Novec 1230) has excellent electrical insulation and low discharge pressure, resulting in less damage to internal equipment and buildings |
Comparison of charging costs by fire extinguishing agent
Please refer to unburnt equipment provided by Dong Nam... HERE
You can refer to the manufacturer for more information....HERE
You will receive a quote from us as soon as possible..