Fire Alarm Center GST GST-IFP4M
GST-IFP4M : Address of Fire Alarm Center UL Standard GsT Fire Alarm Device , Free installation consultation, 12 months warranty ,Best equipment price today in Ho Chi Minh City ,Hotline 0917.911.114
Features of GST Fire Alarm Center GST-IFP4M
☆ Wide range power supply 100 - 240V 50 / 60Hz Multi-language
☆ Programmable via PC or panel keyboard and touch screen
☆ USB port for system configuration and firmware update
☆ Password and non-volatile memory protected by lock
☆ Support USB dongle to protect project database ☆History of 100,000 events
☆ Try an experimental walk, silent or sound
☆PAS (Active Alarm Chain) per point
☆ Optional redundant CPU
☆ CAN / Fiber optic network, panel group 7 inch 800 x 480 touch screen Supports up to 6 loops in type A
☆ 242 addressable devices per ring mixing different device types, Max. 1452 addresses
☆ Supports up to 32 ZCP control panels with individually programmable buttons and LEDs. Up to 8 ZCP panels for wall cabinets)
☆ 2 Limiting Class B Announcement Device Circuit (BAC), maximum total load.2.5A / 24VDC. The 2nd NAC can be set as AUX. Enter 1 define user
☆ 5 system outputs (Contact Form C), Fire, Trouble, Monitoring / F.P.E. and 2 User defined
☆ Built-in printer and additional USB printer interface port for external printer
☆ Integrated protocol to voice alarm system, communication via onboard RS232 port BACnet and Modbus support -
☆ UL listed Specifications Standard Fire Alarm Center GST GST-IFP4M : 10th Edition of UL864 / NFPA72
☆ Main input voltage: 220/230 VAC (+ 10 / -15%) 50/60 Hz
☆ Rated input current: 3.0A (120VAC) or 1.5A (220AC) System operating voltage: 24 VDC nominal
☆ Loop power: 6
☆Device capacity: 242 devices per loop
☆ NAC Output: 2 Class B, Power Limit NAC, Max Total Current 2.5A@24VDC
☆ Relay output (5): 2A @ 24VDC
☆ Operating environment: 32-120 °F, 93% rh, non-condensing
☆ Dimensions: 516mm (W) x 840mm (H) x 180mm (D)