DI-M9319 ,Communication module with GST common detector
Module for communicating with conventional GST detectors: DI-M9319 Price list of the latest GST fire alarm devices, Southeast Company sends to customers, 12 month warranty on fire alarm equipment nationwide, Contact Contact us right away for 24/7 consultation
Basic features DI-M9319 : Module for communicating with GST . conventional detectors
☆ Monitor input port cable with 4.7KΩ EOLR
☆ Monitor power supply.
☆ Two stats for fire and bugs.
☆ Normally open or normally closed output automatically according to input port to change state
☆ Electronic address. The address can be modified in the field.
☆ LED Status Indicator
☆Din-Rail mount or surface mount
☆ Compatible with GST-M200 and GST-IFP4M Fire Alarm Control Panels (FACP). UL approved
Specifications DI-M9319 : Communication module with GST . conventional detector
☆ Operating voltage: Loop 24 VDC (16VDC - 28VDC)
☆ Power supply voltage: Limited voltage 24 VDC (20VDC - 28VDC)
☆ Currently waiting: - 0.38mA . loop - 18mA . capacity
☆ Current action: - 0.39mA . loop - 60mA . capacity
☆ Output power: 2A @ 30VDC, 0.35PF ☆ Input port voltage: 16.8VDC - 27.6VDC
☆ 30 detectors or manual call points or 9 detectors with remote indicator
☆ Working environment:
- Temperature: 0 - + 49
- Relative humidity≤ 93%, no condensation
☆ Dimensions: 85.3mm × 78mm × 33mm