To expand the network of fire detection system detect 3000, basic version, wall cover or 19 "version without power source:
• Transmit signals monitor: (400 mA)
• Includes bitbus interface for connector connection
•9 open collector outputs (30V/90mA)
• 128 programmable detector arlam zones
• 3 relay outputs no electric pressure (250 V/5A)
• External power supply by central control panel or power supply
• Control panel and power supplies include detect thin 3004 and main or secondary language
• It is necessary to have a separate primary ABF control panel and display in the fire alarm network
Technical specification:
– Operating voltage: 21,0 to 29,2 VDC
– Power supply :72 Watt
– Emergency power: max. 2 x 12 V/12 Ah
– Protection layer: IP 30
– Color cover: Light gray, RAL 7035
– Adio signal output 24 VDC/400 mA oversee
– Voltage for external applications: 24 V DC/800 mA
–Relay out pay 3 convey 250
– Pole open output: 9 Pole open 30 VDC/90 mA
– Color front: tele grey, RAL 7046
– Material: Steel sheet
– Stable line: 132 mA
– Warning line 192 mA
– Control 2 x RS-232, RS-422 (option), bitbus (option)
– Display unit: LCD 4 x 20 leters
– Operating temperature: -5°C to 40°C
– Degree of humidity max. 95 %– Sizex R x S)
RDCP 262 mm x 420 mm x 83 mm
RDCP 19″ 6HE x 19” x 83 mm