Notifier XP-6MA fire alarm control module, Normal interface Modle
Notifier XP-6MA 6 zone interface fire alarm control module
⭐Instruction on how to connect r2ml module, how to connect fire alarm module, Provide normal detector control module, addressable control module, cm module, geo-isolation module only, dcp-dimm , 12 month warranty, contact 0917.911.114
General description Fire alarm control module Notifier XP-6MA
- Notifer's six-zone interface the XP6-MA module provides an interface between the smart alarm system and the conventional two-wire detection zone. Common Point The SLC input is used for all modules and initiates common shared device circuits providing external and ground monitoring. On the other hand, each module works independently of the others.
- The first module is addressed 01 to 154 while the remaining modules are automatically assigned to the next higher address fve. Provisions are included to disable up to two people not using the module. The XP6-MA transmits the status of an area of the two-wire detector to the alarm control panel. Report status as normal, open, or alarm. The interface module monitors the detector area and the connection of the external power supply.
- Each XP6-MA module has a dual-color LED panel. The control panel may cause the LED to blink.
Features of Notifier XP-6MA fire alarm control module
• Six address initialization device circuits.
• Plug-in 0.75 mm2 to 1.5 mm2 detachable terminal block.
• Status indicators for each point.
• Unused addresses can be disabled (up to 2).
• Rotary address switch.
• FlashScan® or CLIP operation.
• Includes mounting hardware.
Specifications Fire alarm control module Notifier XP-6MA
- Standby current: 2.20 mA (SLC current drawing with all addresses used; if some addresses are disabled, standby current decreases).
- Alarm current: 40 mA (assuming all six solid LEDs ON).
- Temperature range: 10°C to +55°C
- Humidity: 10% to 93% without air conditioning
- Dimensions: 172.72 mm high x147.32 mm x 31.75 mm deep. Ruler: 0.75 mm2 to 1.5 mm2.
- Maximum SLC wire resistance: 40 or 50 ohms, depends on the panel.
- Maximum IDC wire resistance: 25 ohms.
- External supply voltage:
- External supply voltage: DC voltage: 18 - 28 volt limit voltage.
- Ripple voltage: 0.1 Vrms max. External power supply: up to 90 mA per alarm address