Fire Alarm Center Addressable 2 loop Notifier AM-8200 (159 addresses)
Provide fire alarm control panel with 4 zone horing
⭐ viking tyo 325 5 channel fire alarm control panel, Warranty for 24 channel hochiki fire alarm control panel ,quote for fire alarm system hochiki notifier,fire alarm center 5 zone , 2-channel fire alarm cente, Contact pcccdongnam.vn to get a quote for tyco open viking nozzle
Addressable 2-ring system with Advanced/Opal and CLIP protocols and 7" color touchscreen. Expandable to 4 rings with LIB-8200 card. Each LIB can manage up to 700 logical addresses linked to individual sensor components and modules, each with a physical sequence number up to 159 + 159. The new AM-8200 series allows 2 rings to be placed in each LIB, thanks to the configuration of additional sub-addresses, e.g. siren with blinking light with physical address 9 - sub-address 9.1 (horn) - 9.2 (intermittent.) The ability to configure each loop in CLIP mode (99 + 99) is compatible with sensors and modules with this protocol. 750mA per round. CanBus expandable network with AM82-2S2C card. Certified according to EN 54-2 and EN 54-4.
- Supply rated: 110 - 230 Vac
- Rated frequency: 50 - 60 Hz
- Output voltage: 27.5 Vdc
- Maximum output current 3.5 A
- Maximum loop current. 750 mA
- Minimum battery capacity 12Ah. up to 17Ah
- Operating temperature -5°C ... 40°C
- Relative humidity 5 ... 95% (non-condensing)
- IP protection index 30
- Weight approx. 7 kg (without battery)
- Maximum ring length. 3000 m
- Dimensions A: 369.8 mm H: 445.7 mm F: 111 mm
- Certificate 1293-CPR-0537; EN 54 - A total of 4 access levels, according to EN54.
- Programmable texts: hours: 32 characters; in range: 32 characters.
- 500 physical zones and 400 logical groups for autonomous configuration.
- CBE ("Event-Driven") control equations to trigger with logical operators (AND, OR, DEL, etc.).
- History storage with 2000 events in non-volatile memory. Real-time clock. -
Self-programming loops with automatic identification of device types.
- Decision algorithms for alarm, pre-alarm and fault criteria
- Automatically change the sensitivity of Day/Night.
- Specify the need to clean the sensor.
- Programmable alarm thresholds for sensors.
- Function to check by area.
You can refer to products genuine fire alarm equipment...HERE
You will receive a quote from us as soon as possible..
Have 0 comment, evaluate about Fire Alarm Center Addressable 2 loop Notifier AM-8200 (159 addresses)
TVAdministratorsAdministrators